|

Introduction
Designing a Structured Cabling System - a ten step HOWTO guide
Steps
Below we have provided a ten step introductory guide for the Design of Structured Cabling Systems and IT Network Infrastructures.
Step 1: Which group of standards will you conform to?
European Union CENELEC EN standards America ANSI/TIA/EIA standards Canada CSA standards Australia/New Zealand AS/NZ standards Rest of the World ISO/IEC standards
The three principle design standards give the details of how to design and specify a structured cabling standard, they are;
- ISO 11801
- EN 50173
- TIA/EIA 568-A or 568-B
These standards in turn however refer to hundreds of other standards relating to component specifications, fire performance, testing methods, containment systems etc.
Step 2: Horizontal cabling - Basic rules
Four-pair cables are run from user positions to a patch panel. At the patch panel, patch cords link into the active LAN (Local Area Network) equipment or into backbone cabling. The user position has a wall outlet or floor outlet, and this links into the PC on your desk via another patch cord. The outlet is a called a TO (Telecommunications Outlet) and contains an eight conductor plug meeting IEC 60603-7, more commonly referred to as an RJ-45.
- Two outlets per work area
- Two outlets per 10 square meters of useable floor space
- Outlets to be within 3 meters of the user station
- Both outlets to be RJ 45
- Max cable run to be 90 m
- Max total length of patch cords at both ends of the link to be 10 m
- Cable and RJ45 to be Cat5e or higher grade
Options
Cat 3 for or optical fiber can be used
If optical fiber, select 50/125 or 62.5/125 multimode
If using fiber select SC or ST connectors
Cat 6/Class E can be specified
Cat 5e Cable can be unscreened, UTP, Foil screened, FTP, or Foil and Braid screened S-FTP.
Cable fire performance can be:
- IEC 332-1
- IEC 332-1, IEC 754, IEC 1034
- IEC 332-3-c. IEC 754, IEC 1034
- UL 910 plenum
Each grade, in ascending order, has a better performance in fire situations but at a correspondingly higher price.
The exact density of cables, number of outlets and their position is up to the end user, or else at the proposal of the installer/designer
Step 3: Backbone Cabling
All of the horizontal cables are star-wired back to Telecommunications Closets or Floor Distributors where they are terminated in patch panels. These patch panels are connected together via the building backbone cabling which can be up to 500 meters long. It can be copper cable but is more likely to be optical fiber, either multimode or singlemode. The kind of cables and the number of cores needs to be decided. If fiber is chosen, a loss budget should help you make your decision
Step 4: Campus Cabling
The campus cabling links different buildings together. It can be up to 1500 m long. It can be copper cable but is more likely to be optical fiber, either multimode or singlemode. The kind of cables and the number of cores needs to be decided.
Step 5: Positioning and design of Telecommunications Closets to link horizontal and backbone cabling.
Positioning and design of the equipment room as a central focus for the main computing, LAN and PABX equipment.
Positioning and design of the Service Entrance facility whereby outdoor cables are terminated and the point of demarcation between customer owned equipment and the PTT cables is defined.
Step 6: Cable containment system
How will the cables be protected? Within buildings the choices are:
- Cable trays
- wire basket/raceway
- cable ladders
- J hooks
- conduit
- dado rails
- PVC trunking
- built-in under floor duct
- raised floors
- suspended ceilings
The following must be taken into account:
- the density and volume of cables to be organized
- the aesthetic appearance of the cabling within offices and other visible areas
- economics of different schemes
- proximity to power cables and other potential sources of interference
- fire stopping
Useful standards are:
- TIA/EIA 569 Commercial building standard for telecommunications pathways and spaces
- EN 50174 Information technology – cabling installation
For external applications the choices are:
- underground cable ducts
- direct buried cable trench
- concrete cable trough
- self supporting aerial cable
- supported aerial cable, i.e. catenary or messenger wire
- fixed to building exteriors
In all cases the designer must ensure that all civil work has been carried out, rights of way established and availability of cable ducts and manholes established. Aerial cable routes must keep a minimum distance away from power cables and all external cables must be selected for the environment and temperature ranges in which they are expected to survive. External copper cables usually need to be protected by over voltage and fault current devices where they enter a building.
Step 7: Cable Administration system
The cabling and its containment system need to be clearly identified and their locations, routes and capabilities recorded in a cable administration system. This usually involves a logical numbering scheme that can be applied to all cables, outlets, patch panels and even containment systems. Various color schemes are also available.
These schemes can be paper based but for the larger installations then a computer based system is advisable. There are several proprietary solutions on the market which offer various data base and graphical methods for keeping track of cabling assets. Some systems are also active in that they can detect moves and changes and automatically update the database.
Useful standards are:
- TIA/EIA-606 Administration standard for the telecommunications infrastructure of commercial buildings
- EN 50174 information technology – cabling installation
Step 8: Earthing Scheme
All exposed metallic elements of the cable system and cable containment system need to be earthed (grounded) for safety and also electromagnetic compatibility requirements. If screened cables are used then special attention must be given to effective bonding of the screening elements. Poorly earthed screened cabling may behave worse than unscreened cabling.
An electrically ‘clean’ earth must be available at all points where the cabling is terminated, but especially within telecommunication closets, equipment rooms and service entrances. A clean earth is usually defined as a conductive element with not more than 1 volt rms potential difference between it and the real earth down below. Copper cabling linking two different buildings can suffer from earth loops if the ground potential is different. Non-metallic optical cabling is usually picked for problem areas such as these.
Some useful standards are:
- PrEN50303 Application of equipotential bonding and earthing at premises with information technology equipment
- PrEN50174-2 Information Technology, Cabling installation, part 2, Installation, planning and practices inside buildings
- TIA/EIA-607 Commercial Building Grounding and Bonding Requirements for Telecommunications
Step 9: Testing regime
All cables must be tested to demonstrate compliance with the standards and specification to which they were bought. Testing can be split into copper cable testing and optical fibre testing. Ideally all cables should be 100% tested.
Copper cables.
There are five manufacturers of hand held copper cable testers that will automatically test the installed cable plant for all the expected parameters. By the use of a remote injector, the cabling is tested from both ends, which is a condition of the standards. The cabling has to pass all of the suite of tests to be awarded and overall pass. Points to remember are;
What is being tested? the channel (i.e. end-to-end including all the patch cords) or the basic link (i.e. the permanently installed cable from outlet to patch panel). The test figures are different for each setting. It is usually more practical to test the basic link (also referred to as the permanent link).
What level is being tested? The tester should normally be set to Cat5e link or Class E link if Category 6 cable is being used.
The results are stored electronically and must be in a format recognizable by the cable management software that comes with the tester. There are now numerous test standards and draft standards. The most influential is likely to be;
IEC 61935 Generic specification for the testing of balanced generic cabling in accordance with ISO/IEC 11801
The tests required are; IEC 61935 Wire Map X Attenuation X; NEXT pair to pair X; NEXT Powersum X; ELFEXT air to pair X; ELFEXT Powersum X; Return Loss X; Propagation Delay X; Delay Skew X;DC Loop Resistance X. Cable length and ACR are also useful additions to this set of tests.
Optical cables
All that needs to be tested with short distance multimode optical cables is attenuation. This can be achieved by a device called a light source and power meter. This device will simply measure the absolute loss across the optical link. This then has to be compared with the design value of attenuation. If the tested value is less than the design value then the link can be seen to be acceptable.
Optical Time Domain Reflectometers can give a great deal of information about optical fibers, but for short haul multimode fiber they are an expensive overkill that gives results that need expert interpretation. An OTDR remains an essential tool for fault finding.
Step 10: Final thoughts
Is the design of the cabling system in-step with the LAN aspirations of the end user? For example, Cat5e is the minimum performance grade suitable for gigabit Ethernet. Standard Cat5 cable may not have sufficient delay skew performance for RGB video systems however. Cat 6 cabling will give a longer service life due to its higher performance, but at an initial higher cost.
Some optical fiber LANs, e.g. gigabit Ethernet cannot transmit over the full distance allowed in standards based optical structured cabling. These LAN limitations have to be taken into account. The next generation of 10 gigabit Ethernet will need a new generation of optical fiber to make it work. International standard ISO/IEC 11801 specifies general-purpose telecommunication cabling systems Structured Cabling that are suitable for a wide range of applications (analog and ISDN telephony, various data communication standards, building control systems, factory automation). It covers both balanced copper cabling and optical fiber cabling. The standard was designed for use within commercial premises that may consist of either a single building or of multiple buildings on a campus. It was optimized for premises that span up to 3 km, up to 1 km˛ office space, with between 50 and 50,000 persons, but can also be applied for installations outside this range. A corresponding standard for small-office/home-office (SOHO) environments is ISO/IEC 15018, which covers also 1.2 GHz links for cable and satellite TV applications.
The above information is offered as a summary of ISO 11801 and related standards. It is not a definitive design guide and does not replace study and implementation of the Standards themselves. The publisher accepts no responsibility for inaccuracies or omissions.
General Information Structured Cabling is defined as building or campus telecommunications cabling infrastructure that consists of a number of standardized smaller elements (hence structured) called subsystems.
Structured cabling falls into the following six sub-systems:
- Entrance Facilities is where the building interfaces with the outside world.
- Equipment Rooms host equipment which serves the users inside the building.
- Telecommunications Rooms are where various telecommunications and data equipment resides, connecting the backbone and horizontal cabling sub-systems.
- Backbone Cabling as the name suggests carries the signals between the entrance facilities, equipment rooms and telecommunications rooms.
- Horizontal Cabling is the wiring from telecommunications rooms to the individual outlets on the floor.
- Work-Area Components connect end-user equipment to the outlets of the horizontal cabling system.
Structured cabling design and installation is governed by a set of standards that determine how to wire a data center, office or apartment building for data or voice communications, using Category 5 or Category 6 cable and modular sockets. These standards define how to lay the cabling in a star formation, such that all outlets terminate at a central patch panel (which is normally 19 inch rack-mounted), from where it can be determined exactly how these connections will be used. Each outlet can be 'patched' into a data network switch (normally also rack mounted alongside), or patched into a 'telecoms patch panel' which forms a bridge into a private branch exchange (PBX) telephone system, thus making the connection a voice port.
Lines patched as data ports into a network switch require simple straight-through patch cables at the other end to connect a computer. Voice patches to PBXs in most countries require an adapter at the remote end to translate the configuration on 8P8C modular connectors into the local standard telephone wall socket. In the U.S., no adapter is needed, as the 6P6C plug used with RJ11 telephone connections is physically compatible with the larger 8P8C socket and the wiring of the 8P8C is compatible with RJ11. In the UK, an adapter must be present at the remote end as the 6-pin BT socket is physically incompatible with 8P8C.
It is normal to see different colour patch cables used in the patch panel to help identify which type of connection is being carried, though the structured cabling standards do not require this, except in the demarcation wall field
The standards demand that all eight connectors in the Cat6 cable are connected, resisting the temptation to 'double-up' or use one cable for both voice and data. This is generally a good thing as it means that they fully support features such as Power over Ethernet which require the so-far unused brown pair of the 4pr. cable.
Category 7 cable (CAT7), (ISO/IEC 11801:2002 category 7/class F), is a cable standard for Ethernet and other interconnect technologies that can be made to be backwards compatible with traditional CAT5 and CAT6 Ethernet cable. CAT7 features even more stringent specifications for crosstalk and system noise than CAT6. To achieve this, shielding has been added for individual wire pairs and the cable as a whole.
The CAT7 cable standard has been created to allow 10 gigabit Ethernet over 100 meters of copper cabling. The cable contains four twisted copper wire pairs, just like the earlier standards. CAT7 can be terminated either with RJ-45 compatible GG45 electrical connectors which incorporate the RJ-45 standard or with TERA connectors. When combined with GG-45 or TERA connectors, CAT7 cable is rated for transmission frequencies of up to 600 MHz.
|